HFC-152a, 1,1-Difluoroethane
| Chemical name | 1,1-Difluoroethane |
|---|---|
| Common names / synonyms | R152a, HFC-152a, Difluoroethane, Genetron 152a, Dymel 152a |
| CAS number | 75-37-6 |
| UN number | 1030 (1,1-Difluoroethane, flammable liquefied gas) |
| Dangerous goods code | 21017 (Class 2.1 Flammable gas) |
| Molecular formula | C2H4F2 (CH3CHF2) |
| Molecular weight | 66.05 g/mol |
| Recommended use | Refrigerant (mixture component, candidate alternative to R404A/R507A), aerosol propellant, polyurethane blowing agent, organic Rankine cycle working fluid, automotive air conditioning alternative candidate, etc. |
| Supplier name | Anhui Kelvins Refrigeration Technology Co., Ltd. |
|---|---|
| Address | Room 302, Building B, No. 396 Songgu Road, Hefei, China |
| Postal code | 230601 |
| Telephone | +86 551 6558 9290 |
| Fax | +86 551 6558 9290 |
| sales@klven.cn |
National Chemical Emergency Hotline (China): +86-532-83889090 (24 hours)
Zhejiang Chemical Emergency Hotline: +86-571-88071797
Supplier Emergency Contact: +86 551 6558 9290
Note: R152a is an ASHRAE A2-class (low toxicity, flammable) refrigerant. GWP is only 124, making it a candidate low-GWP environmentally friendly alternative. However, it is highly flammable (explosive limits 3.9%–16.9%), and strict fire and explosion prevention measures must be taken during use.
Signal word: Danger
This product is a pure substance.
| Component name | CAS No. | Concentration (by mass) |
|---|---|---|
| 1,1-Difluoroethane | 75-37-6 | ≥99.5% |
| Impurity | Specification limit |
|---|---|
| Acidity (as HCl) | ≤1 ppm |
| Moisture | ≤10 ppm |
| Evaporation residue | ≤100 ppm |
| Non-condensable gas | ≤1.5% |
| Chloride | Pass |
General advice: Remove victim from contaminated area immediately. Keep warm and at rest. Show this SDS to attending physician. Eliminate all ignition sources.
Inhalation:
Skin contact (frostbite):
Eye contact:
Ingestion:
Not applicable. This substance is a gas at ambient temperature; ingestion exposure is not expected.
Suitable extinguishing media: Dry chemical, carbon dioxide. If the leaking gas cannot be safely stopped, allow the gas to burn and use water fog to cool the surrounding environment.
Unsuitable extinguishing media: Direct water stream (limited effectiveness on gas fires).
Hydrogen fluoride (HF), carbon monoxide (CO), carbonyl fluoride (COF₂), and other fluorinated compounds.
See Section 8 (Exposure controls/personal protection) and Section 13 (Disposal considerations).
For industrial use only. Personnel must be professionally trained. R152a is primarily used as a mixture refrigerant component, aerosol propellant, and blowing agent. As a low-GWP (124) environmentally friendly alternative candidate, it may be used in automotive air conditioning and commercial refrigeration. Do not use for direct food contact, medical inhalation, or other unapproved applications.
| China OEL (Occupational Exposure Limit) | No established legal limit. Recommended reference: AIHA WEEL 1000 ppm (TWA, 8 hr) |
|---|---|
| AIHA WEEL-TWA (USA) | 1000 ppm (time-weighted average, 8-hour) |
| OSHA PEL-TWA (USA) | Not established |
| DFG MAK (Germany) | 1000 ppm (reference value) |
| Biological limit value | Not established |
Note: Per GBZ 2.1-2019, this substance is not currently listed in the Chinese OEL table. International standards are recommended as reference during operation. NOAEL is 50,000 ppm.
Gas chromatography with flame ionization detection (GC-FID) or mass spectrometry (GC-MS), infrared spectroscopy, combustible gas detector.
Respiratory protection:
Eye/face protection:
Skin protection:
| Appearance and odor | Colorless gas with a faint ethereal odor; gaseous at ambient temperature and pressure; colorless transparent liquid under pressure |
|---|---|
| Odor threshold | Not available (faint ether-like odor) |
| pH | Not applicable (gas) |
| Melting point / Freezing point | −117 °C (−178.6 °F) |
| Boiling point / Boiling range (101.3 kPa) | −24 °C (−11.2 °F) |
| Flash point | −50 °C (−58 °F) (extremely flammable) |
| Evaporation rate | Not available |
| Flammability (gas) | Extremely flammable (Category 1A) |
| Explosive limits (upper/lower) | Lower 3.9% (vol) / Upper 16.9% (vol) |
| Vapor pressure (25°C) | 430 kPa (saturated vapor pressure) |
| Vapor density (air = 1) | ~2.28 (heavier than air) |
| Relative density (liquid, 25°C) | 0.901 g/cm³ |
| Solubility | Slightly soluble in water; soluble in ethanol, ether, and other organic solvents |
| Octanol/water partition coefficient (log P) | ~0.75 (estimated) |
| Auto-ignition temperature | 458 °C (856.4 °F) |
| Decomposition temperature | >300 °C onset of thermal decomposition |
| Viscosity (gas, 25°C) | ~9.3 μPa·s |
| Surface tension (liquid, 25°C) | ~6.5 mN/m |
| Critical temperature | 113.3 °C (235.9 °F) |
|---|---|
| Critical pressure | 4520 kPa (4.52 MPa / 655.5 psia) |
| Critical density | 0.365 g/cm³ |
| Heat of vaporization (at boiling point) | 324 kJ/kg |
| Liquid specific heat (25°C) | 1.68 kJ/(kg·°C) |
| Henry's Law constant (25°C) | ~8.0 × 10⁻¹ mol/(m³·Pa) (estimated) |
| ASHRAE safety group | A2 (low toxicity, flammable) |
|---|---|
| Ozone Depletion Potential (ODP) | 0 (does not deplete ozone layer; see Section 12.6) |
| Global Warming Potential (GWP, 100-yr) | ~124 (low GWP, environmentally friendly alternative; see Section 12.6) |
Chemically relatively stable under normal temperature and pressure, but highly flammable.
Stable under normal conditions of temperature and pressure, but must be kept away from fire and heat sources.
High temperature, open flame, sparks, static electricity, direct heat sources, cylinder overpressure.
Reactive metals (sodium, potassium, calcium, aluminum powder, magnesium powder, etc.), strong oxidizing agents.
Hydrogen fluoride (HF), carbon monoxide (CO), carbonyl fluoride (COF₂), and other fluorinated compounds.
Will not occur.
Acute toxicity:
| Rat inhalation LC50 (4 hr) | 383,000 ppm (38.3% by volume) |
|---|---|
| Mouse inhalation LC50 (2 hr) | Not available |
| Rabbit dermal LD50 | Not available (gaseous substance) |
Liquid contact can cause frostbite (physical injury), but is not a chemical corrosive. GHS classification: no skin corrosion/irritation classification (physical frostbite only).
Liquid contact can cause severe frostbite and corneal damage. GHS classification: not separately classified (physical frostbite).
No sensitization reported. Available animal test data and human epidemiology data show no sensitization effect.
In vitro and in vivo tests (Ames test, chromosome aberration test, mouse micronucleus test, etc.) show no mutagenic effect.
Insufficient evidence for carcinogenicity.
Animal studies show no significant reproductive or developmental toxicity at or below the NOAEL (50,000 ppm). No human reproductive toxicity data available.
Repeated low-concentration exposure shows no significant target organ toxicity. Long-term animal inhalation studies (NOAEL 50,000 ppm) have not shown clear organ damage.
Not expected to cause aspiration pneumonia in gaseous form. However, high-concentration inhalation can cause CNS depression and cardiac sensitization. Deliberate inhalation (abuse) may cause severe cardiac arrhythmia or even sudden death.
| Fish acute toxicity (LC50, 96 hr) | >100 mg/L (low toxicity to fish) |
|---|---|
| Daphnia acute toxicity (EC50, 48 hr) | >100 mg/L |
| Algae growth inhibition (EC50, 72 hr) | >100 mg/L |
| Bacterial toxicity | Not available |
log P ≈ 0.75. Low bioaccumulation potential (below the bioconcentration threshold of log P = 4.5).
Highly volatile in gaseous form. Low water solubility. Relatively high mobility. Volatilizes readily to atmosphere when released to soil.
Does not meet PBT (persistent, bioaccumulative, and toxic) / vPvB (very persistent and very bioaccumulative) criteria.
Product/residues:
Contaminated packaging:
1030 (1,1-Difluoroethane, flammable liquefied gas)
1,1-DIFLUOROETHANE
Class 2.1 Flammable gas
Not applicable (Class 2 gases are not assigned a packing group)
Road transport:
Rail transport:
Marine transport (IMDG Code):
Air transport (ICAO/IATA DGR):
China regulations:
International regulations:
Chemical Safety Assessment has not been carried out for this substance in the context of this SDS. Users should conduct their own assessment based on specific use conditions.
| Abbreviation | Full term |
|---|---|
| SDS / MSDS | Safety Data Sheet / Material Safety Data Sheet |
| GHS | Globally Harmonized System of Classification and Labelling of Chemicals |
| CAS | Chemical Abstracts Service (registry number) |
| UN | United Nations (dangerous goods number) |
| ODP | Ozone Depletion Potential |
| GWP | Global Warming Potential |
| LC50 | Lethal Concentration, 50% |
| LD50 | Lethal Dose, 50% |
| NOAEL | No Observed Adverse Effect Level |
| WEEL | Workplace Environmental Exposure Level |
| SCBA | Self-Contained Breathing Apparatus |
| PBT | Persistent, Bioaccumulative, and Toxic |
| HFC | Hydrofluorocarbon |
| BLEVE | Boiling Liquid Expanding Vapor Explosion |
This Safety Data Sheet (SDS) has been prepared in accordance with GB/T 16483-2008 and the UN GHS standard, and is intended to provide guidance on the safe use, handling, and disposal of this product. The information contained herein is based on publicly available chemical databases, technical literature, and national standards, and is believed to be accurate and complete as of the date of issuance. However, no warranty, express or implied, is made as to the absolute accuracy, completeness, or reliability of the information. Users should verify the applicability of the information for their specific use conditions and local regulatory requirements, and take necessary safety precautions. The information in this document may be updated as new research findings and regulatory changes become available; periodic review of the latest version is recommended.
This Safety Data Sheet (SDS) is compiled by Kelvins for technical reference, prepared in accordance with GB/T 16483 and GB/T 17519. For the official SDS and batch inspection report, please contact us. If any data on this page is inconsistent with the manufacturer’s latest published version, the manufacturer’s official document shall prevail.
After submitting your request, our technical consultant will contact you within 2 hours with model recommendations and the latest prices.