Opteon XP5, HFO/HFC blend
| Chemical name | Refrigerant R513A (HFO/HFC blend) |
|---|---|
| Common names / synonyms | R513A, R-513A, Opteon XP5 (Chemours brand), HFO/HFC blend |
| CAS number | No single CAS number (mixture; see composition information) |
| UN number | 3161 (liquefied flammable gas) |
| Dangerous goods code | Class 2.1 Flammable gas |
| Composition | R1234yf (56% by mass) + R134a (44% by mass) |
| Molecular weight | 108.6 g/mol (weighted average of mixture) |
| Recommended use | Direct replacement refrigerant for R134a, commercial refrigeration, automotive air conditioning, chillers, vending machines, etc. |
| Supplier name | Anhui Kelvins Refrigeration Technology Co., Ltd. |
|---|---|
| Address | Room 302, Building B, No. 396 Songgu Road, Hefei, China |
| Postal code | 230601 |
| Telephone | +86 551 6558 9290 |
| Fax | +86 551 6558 9290 |
| sales@klven.cn |
National Chemical Emergency Hotline (China): +86-532-83889090 (24 hours)
Supplier Emergency Contact: +86 551 6558 9290
Note: R513A is classified as ASHRAE safety group A2L (lower toxicity, lower flammability). The flammability is inherited from the R1234yf component (56%). It is only flammable under specific concentration conditions (~8.7%-12.0% by volume in air) and with a strong ignition source. Burning velocity is extremely low (<10 cm/s), making it far more difficult to ignite than conventional flammable gases. Frostbite from liquid contact is a physical low-temperature injury.
Signal word: Warning
Note: H316/H320 are standard GHS hazard statement codes. The skin/eye injury mechanism is physical cryogenic frostbite; the codes are used to represent similar hazard effects. Flammability is inherited from the R1234yf component (56%); the R134a component (44%) is itself non-flammable.
This product is a mixture, blended from two refrigerants in a fixed ratio.
| Component name | CAS No. | Molecular formula | Concentration (by mass) |
|---|---|---|---|
| 2,3,3,3-Tetrafluoropropene (R1234yf / HFO-1234yf) | 754-12-1 | CF3CF=CH2 (C3H2F4) | 56% |
| 1,1,1,2-Tetrafluoroethane (R134a / HFC-134a) | 811-97-2 | CH2FCF3 (C2H2F4) | 44% |
| Mixture type | Near-azeotropic blend (near-azeotropic refrigerant) |
|---|---|
| Temperature glide | <0.5°C (minimal; near-azeotropic behavior) |
| Composition stability | Composition ratio remains nearly constant in both liquid and vapor phases; suitable for direct-expansion refrigeration systems |
| Impurity | Specification limit |
|---|---|
| Acidity (as HCl) | ≤1 ppm |
| Moisture | ≤10 ppm |
| Evaporation residue | ≤100 ppm |
| Non-condensable gas (25°C, vol%) | ≤1.5% |
| Chloride | Pass |
General advice: Remove victim from contaminated area immediately. Keep warm and at rest. Show this SDS to attending physician. Eliminate all ignition sources.
Inhalation:
Skin contact (frostbite):
Eye contact:
Ingestion:
Not applicable. This substance is a gas at ambient temperature; ingestion exposure is not expected.
Suitable extinguishing media: This substance is an A2L (low-flammability) gas and is only combustible under specific conditions. Dry chemical powder, carbon dioxide, water fog, and foam are acceptable.
Unsuitable extinguishing media: Avoid direct water jets on leaking gas (may accelerate dispersion and evaporation). Water spray may be used to cool containers.
Hydrogen fluoride (HF), carbon monoxide (CO), carbonyl fluoride (COF₂), and other fluorinated compounds.
See Section 8 (Exposure controls/personal protection) and Section 13 (Disposal considerations).
For industrial use only. Personnel must be professionally trained. Suitable for commercial refrigeration, automotive air conditioning, chillers, vending machines, supermarket refrigeration/freezing, etc. As a direct replacement for R134a, it can be charged directly into existing R134a systems (56% GWP reduction compared to R134a). Do not use for direct food contact, medical inhalation, or other unapproved applications.
| China OEL (Occupational Exposure Limit) | No established legal limit. Recommended to reference international standards for each component. |
|---|---|
| R1234yf component — AIHA WEEL-TWA | 500 ppm (approx. 2400 mg/m³), 8-hour time-weighted average |
| R134a component — ACGIH TLV-TWA | 1000 ppm (approx. 4170 mg/m³), 8-hour time-weighted average |
| Mixture recommended limit | Use the more conservative R1234yf limit of 500 ppm as the operational reference for the mixture |
| Biological limit value | Not established |
Note: Per GBZ 2.1-2019 (Occupational exposure limits for hazardous agents in the workplace — Part 1: Chemical agents), this mixture is not currently listed in the Chinese OEL table. International standards for each component are recommended as reference.
Gas chromatography with flame ionization detection (GC-FID) or mass spectrometry (GC-MS), or infrared gas analyzers and electrochemical sensors for field monitoring.
Respiratory protection:
Eye/face protection:
Skin protection:
| Appearance and odor | Colorless gas with a faint ethereal odor; gaseous at ambient temperature and pressure; colorless transparent liquid under pressure |
|---|---|
| Odor threshold | Not available (faint ether-like odor) |
| pH | Not applicable (gas) |
| Melting point / Freezing point | Not applicable (mixture, near-azeotropic) |
| Boiling point / Boiling range (101.3 kPa) | -29.2 °C (-20.6 °F) (near-azeotropic; temperature glide <0.5°C) |
| Flash point | None (gas, but has flammability range) |
| Evaporation rate | Not available |
| Flammability (gas) | Flammable (A2L low-flammability; limits ~8.7%-12.0%) |
| Explosive limits (upper/lower) | Upper: ~12.0% (vol); Lower: ~8.7% (vol) |
| Vapor pressure (25°C) | 580 kPa (saturated vapor pressure) |
| Vapor density (air = 1) | ~3.75 (heavier than air) |
| Relative density (liquid, 25°C) | 1.155 g/cm³ |
| Solubility | Slightly soluble in water; soluble in ethanol, ether, and other organic solvents |
| Octanol/water partition coefficient (log P) | ~0.9 (estimated, weighted by components) |
| Auto-ignition temperature | ~630 °C (inherited from R1234yf component) |
| Decomposition temperature | >400 °C onset of thermal decomposition |
| Burning velocity | ~3-4 cm/s (extremely low, A2L characteristic) |
| Temperature glide | <0.5°C (near-azeotropic mixture characteristic) |
| Critical temperature | 99.6 °C (211.3 °F) |
|---|---|
| Critical pressure | 3588 kPa (3.59 MPa / 520.3 psia) |
| Critical density | 0.489 g/cm³ |
| Heat of vaporization (at boiling point) | ~172 kJ/kg |
| Liquid specific heat (25°C) | 1.40 kJ/(kg·°C) |
| Gas specific heat (25°C, constant pressure) | 0.95 kJ/(kg·°C) |
| ASHRAE safety group | A2L (lower toxicity, lower flammability) |
|---|---|
| Ozone Depletion Potential (ODP) | 0 (does not deplete ozone layer; see Section 12.6) |
| Global Warming Potential (GWP, 100-yr) | ~573 (weighted average of R134a and R1234yf; see Section 12.6) |
| Atmospheric lifetime | R1234yf component: ~12 days; R134a component: ~14 years (components degrade independently) |
Chemically stable under normal temperature and pressure conditions; not readily reactive. Not easily ignited under normal operating conditions.
Stable under normal conditions of temperature and pressure. As a near-azeotropic mixture, the components do not chemically react with each other.
High temperature, open flame, direct heat sources, electrical arcs, electrostatic sparks, cylinder overpressure
Reactive metals (sodium, potassium, calcium, aluminum powder, magnesium powder, etc.), strong oxidizing agents
Hydrogen fluoride (HF), carbon monoxide (CO), carbonyl fluoride (COF₂), and other fluorinated compounds
Will not occur.
Acute toxicity:
| Rat inhalation LC50 (4 hr) — mixture | >500,000 ppm (highest concentration tested for the mixture; no lethality observed) |
|---|---|
| R1234yf component — Rat inhalation LC50 (4 hr) | >500,000 ppm |
| R134a component — Rat inhalation LC50 (4 hr) | >500,000 ppm |
| Rabbit dermal LD50 | Not available (gaseous substance) |
Liquid contact can cause frostbite (physical injury), but chemical irritation is mild. GHS classification: Skin irritation Category 3 (mild irritation, H316).
Liquid contact can cause severe frostbite and corneal damage. GHS classification: Serious eye damage/eye irritation Category 2B (H320).
No sensitization reported. Both components (R1234yf and R134a) show no sensitization effect in available animal test data and human epidemiology data.
In vitro and in vivo tests (Ames test, chromosome aberration test, mouse micronucleus test, etc.) for both components show no mutagenic effect.
Neither component has sufficient evidence of carcinogenicity.
Animal studies for both components show no significant reproductive or developmental toxicity at high concentrations. No human reproductive toxicity data available.
Both components show no significant target organ toxicity from repeated low-concentration exposure. Long-term animal inhalation studies have not shown clear organ damage.
Not expected to cause aspiration pneumonia in gaseous form. However, high-concentration inhalation can cause CNS depression and cardiac sensitization.
| Fish acute toxicity (LC50, 96 hr) | >100 mg/L (low toxicity to fish; both components are low toxicity) |
|---|---|
| Daphnia acute toxicity (EC50, 48 hr) | >100 mg/L |
| Algae growth inhibition (EC50, 72 hr) | >100 mg/L |
| Bacterial toxicity | Not available |
log P ≈ 0.9 (weighted estimate). Low bioaccumulation potential (below the bioconcentration threshold of log P = 4.5).
Highly volatile in gaseous form. Low water solubility. High mobility. Volatilizes readily to atmosphere when released to soil.
Does not meet PBT (persistent, bioaccumulative, and toxic) / vPvB (very persistent and very bioaccumulative) criteria.
Product/residues:
Contaminated packaging:
3161 (flammable liquefied gas, N.O.S.)
FLAMMABLE LIQUEFIED GAS, N.O.S. (Refrigerant R513A)
Class 2.1 Flammable gas
Not applicable (Class 2 gases are not assigned a packing group)
Road transport:
Rail transport:
Marine transport (IMDG Code):
Air transport (ICAO/IATA DGR):
International regulations:
Chinese regulations:
Chemical Safety Assessment has not been carried out for this mixture in the context of this SDS. Users should conduct their own assessment based on specific use conditions and the assessments of individual components.
| Abbreviation | Full term |
|---|---|
| SDS / MSDS | Safety Data Sheet / Material Safety Data Sheet |
| GHS | Globally Harmonized System of Classification and Labelling of Chemicals |
| CAS | Chemical Abstracts Service (registry number) |
| UN | United Nations (dangerous goods number) |
| ODP | Ozone Depletion Potential |
| GWP | Global Warming Potential |
| LC50 | Lethal Concentration, 50% |
| LD50 | Lethal Dose, 50% |
| NOAEL | No Observed Adverse Effect Level |
| WEEL | Workplace Environmental Exposure Level |
| TLV-TWA | Threshold Limit Value - Time-Weighted Average |
| PEL | Permissible Exposure Limit |
| SCBA | Self-Contained Breathing Apparatus |
| PBT | Persistent, Bioaccumulative, and Toxic |
| HFO | Hydrofluoroolefin |
| HFC | Hydrofluorocarbon |
| IARC | International Agency for Research on Cancer |
| ACGIH | American Conference of Governmental Industrial Hygienists |
| STOT | Specific Target Organ Toxicity |
This Safety Data Sheet (SDS) has been prepared in accordance with the UN GHS standard and applicable regulatory requirements. The information contained herein is based on publicly available chemical databases, technical literature, and national standards, and is believed to be accurate and complete as of the date of issuance. However, no warranty, express or implied, is made as to the absolute accuracy, completeness, or reliability of the information. Users should verify the applicability of the information for their specific use conditions and refer to the official SDS provided by the manufacturer/supplier for compliance purposes. The information in this document may be updated as new research findings and regulatory changes become available; periodic review of the latest version is recommended.
This Safety Data Sheet (SDS) is compiled by Kelvins for technical reference, prepared in accordance with GB/T 16483 and GB/T 17519. For the official SDS and batch inspection report, please contact us. If any data on this page is inconsistent with the manufacturer’s latest published version, the manufacturer’s official document shall prevail.
After submitting your request, our technical consultant will contact you within 2 hours with model recommendations and the latest prices.