HFO-1233zd(E), trans-1-Chloro-3,3,3-trifluoropropene
R1233zd(E) (trans-1-chloro-3,3,3-trifluoropropene) is a low-GWP, non-flammable low-pressure fluid used in centrifugal chillers, organic Rankine cycle (ORC) and foam blowing. It is an eco-friendly alternative to R123/R245fa.
| Chemical Name | trans-1-Chloro-3,3,3-trifluoropropene |
|---|---|
| Molecular Formula | CF₃CCl=CH₂(trans) |
| Molecular Weight | 130.50 |
| Boiling Point (101.3 kPa) | 18.1 ℃ |
| Critical Temperature | 166.5 ℃ |
| Critical Pressure | 3.62 MPa |
| ODP (Ozone Depletion Potential) | 0.00034 |
| GWP (Global Warming Potential) | < 1 |
| ASHRAE Safety Class | A1 (Non-toxic, Non-flammable) |
| Vapor Density (air = 1) | 4.505 |
| Liquid Density (20/4℃) | 1.2749 |
| Critical Density (g/cm³) | 0.4834 |
| Acentric Factor | 0.3040 |
| Triple Point Temperature (°C) | -107.400 |
| Appearance | Colorless, transparent, free of turbidity |
|---|---|
| Purity | ≥ 99.9 % |
| Moisture | ≤ 10 ppm |
| Acidity (as HCl) | ≤ 1 ppm |
| Evaporation Residue | ≤ 0.01 % |
| Executing Standard | Compliant with national and industry standards |
| 5 / 10 kg | Disposable steel cylinder |
|---|---|
| 100 / 340 kg | Refillable steel cylinder |
R1233zd(E) is non-flammable but a chlorine-containing low-GWP fluid; use and recovery must follow environmental regulations and avoid strong oxidizers.
| Storage & Transportation | Store in a cool, well-ventilated warehouse away from fire and heat; temperature not above 52℃. Keep separated from oxidizers and acids. Inspect cylinders periodically and handle gently. |
|---|
This Technical Data Sheet (TDS) is provided by Kelvins Data are based on current product standards and Wulachem’s finished-product technical references, for reference only; actual parameters are subject to the factory inspection report. For the official MSDS/SDS or batch inspection report, please contact us.
After submitting your request, our technical consultant will contact you within 2 hours with model recommendations and the latest prices.