安徽省合肥市 周一至周六 08:30 - 18:00
Sales Hotline +86 551 6558 9290
R152a

R152a Difluoroethane Refrigerant · Technical Data Sheet (TDS)

HFC-152a, 1,1-Difluoroethane

View Product Details
Chemical Name1,1-Difluoroethane
Molecular FormulaCH₃CHF₂
CAS No.75-37-6
Product CategoryHFC
Safety ClassA2 (Low toxicity, Flammable)

Product Overview

R152a (1,1-difluoroethane) has a boiling point of -25.0℃ and a GWP of only about 148. It is often blended with R32 and others into low-GWP mixtures for residential A/C, automotive A/C and heat pumps.

Physical & Chemical Properties

R152a Refrigerant Physical & Chemical Properties
Chemical Name1,1-Difluoroethane
Molecular FormulaCH₃CHF₂
Molecular Weight66.05
Boiling Point (101.3 kPa)-25.0 ℃
Critical Temperature113.3 ℃
Critical Pressure4.52 MPa
ODP (Ozone Depletion Potential)0
GWP (Global Warming Potential)148
ASHRAE Safety ClassA2 (Low toxicity, Flammable)

Quality Specification

R152a Refrigerant Quality Specification
AppearanceColorless, transparent, free of turbidity
Purity≥ 99.9 %
Moisture≤ 10 ppm
Acidity (as HCl)≤ 1 ppm
Evaporation Residue≤ 0.01 %
Executing StandardCompliant with national and industry standards

Package Specification

R152a Refrigerant Package Specification
5 / 10 kgDisposable steel cylinder
100 / 340 kgRefillable steel cylinder

Product Features

  • 1GWP of only about 148, environmentally friendly
  • 2Boiling point -25.0℃, suited to A/C and heat pumps
  • 3Often blended with R32 etc. into low-GWP mixtures
  • 4Purity ≥99.9%

Applications

  • 1Residential and automotive A/C (blends)
  • 2Air-source heat pumps
  • 3Foam blowing and aerosol propulsion
  • 4Medium-low temperature refrigeration

Safety & Precautions

Safety Notice

R152a is an A2 flammable fluid. Blending and application must follow flammable-refrigerant codes with explosion protection and ventilation, operated by professionals.

Storage & TransportationStore in a cool, ventilated, explosion-proof warehouse away from fire and heat; temperature not above 52℃. Strictly separate from oxidizers. Inspect cylinders periodically and handle gently.

This Technical Data Sheet (TDS) is provided by Kelvins Data are based on current product standards and Wulachem’s finished-product technical references, for reference only; actual parameters are subject to the factory inspection report. For the official MSDS/SDS or batch inspection report, please contact us.

Need a refrigerant quote or selection advice?

After submitting your request, our technical consultant will contact you within 2 hours with model recommendations and the latest prices.