安徽省合肥市 周一至周六 08:30 - 18:00
Sales Hotline +86 551 6558 9290
R454B

R454B HFC/HFO Blend Refrigerant (R410A replacement) · Technical Data Sheet (TDS)

Opteon XL41, Puron Advance, Solstice 454B

View Product Details
Chemical Name制冷剂 R454B(二氟甲烷/2,3,3,3-四氟丙烯混合物)
Molecular Formula
CAS No.混合物(组分 CAS 见 SDS 第3部分)
Product CategoryHFC/HFO Blend
Safety ClassA2L (Low toxicity, Mildly flammable)

Product Overview

R454B low-GWP A2L mildly flammable blend designed to replace R410A in air conditioning and heat pumps.

Physical & Chemical Properties

R454B Refrigerant Physical & Chemical Properties
Chemical Name制冷剂 R454B (二氟甲烷/2,3,3,3-四氟丙烯混合物)
Molecular Weight62.6
Boiling Point (101.3 kPa)bubble point -50.9 ℃ (temperature glide about 1.5 ℃)
Critical Temperature77.0 ℃
Critical Pressure5.27 MPa
Vapor Density (air = 1)2.16
Composition (mass ratio)R-32 / R-1234yf (68.9 / 31.1)
UN Number3161
ODP (Ozone Depletion Potential)0
GWP (Global Warming Potential)466 (AR4)
ASHRAE Safety ClassA2L (Low toxicity, Mildly flammable)

Quality Specification

R454B Refrigerant Quality Specification
AppearanceColorless, transparent, free of turbidity
OdorOdorless
Purity≥ 99.9 %
Moisture≤ 10 ppm
Acidity (as HCl)≤ 1 ppm
Evaporation Residue≤ 0.01 %

Package Specification

R454B Refrigerant Package Specification
10/13.6 kgDisposable steel cylinder
400/800/926 kgRefillable steel cylinder
24 tISO Tank

Product Features

  • 1Low GWP (466), about 78% lower emissions vs R410A
  • 2ASHRAE safety group A2L: mildly flammable, low toxicity
  • 3Cooling capacity close to R410A, mainstream R410A replacement
  • 4Suited to new and replacement AC/heat-pump systems

Applications

  • 1Residential and light-commercial air conditioning and heat pumps
  • 2New and replacement systems for R410A (per OEM approval)
  • 3Industrial and commercial HVAC&R
  • 4Buildings with strict efficiency and compliance requirements

Safety & Precautions

Safety Notice

R454B is an A2L mildly flammable refrigerant. Follow ASHRAE 15 / national standards for ventilation, charge limits and fire prevention. No open flames; ensure good ventilation.

Storage & TransportationStore in a cool, well-ventilated warehouse away from fire and heat; temperature not above 52℃. Keep separated from oxidizers and acids. Cylinders must be periodically inspected.

This Technical Data Sheet (TDS) is provided by Kelvins Data are based on current product standards and Wulachem’s finished-product technical references, for reference only; actual parameters are subject to the factory inspection report. For the official MSDS/SDS or batch inspection report, please contact us.

Need a refrigerant quote or selection advice?

After submitting your request, our technical consultant will contact you within 2 hours with model recommendations and the latest prices.

Inquiry +86 551 6558 9290